| Rev | Date | Description | BY | CHK | APP | |||||
| A | 05-08-2018 | Issued for Review | KVZ | TB | RAR | |||||
| B | 05-10-2018 | Issued for Review | KVZ | TB | RAR | |||||
| 0 | 05-11-2018 | Issued for Purchase | KVZ | TB | RAR | |||||
| 1 | 05-11-2018 | Re-Issued for Purchase | KVZ | TB | RAR | |||||
| 2 | 05-22-2018 | Issued for Review | KVZ | TB | RAR | |||||
| 3 | 05-24-2018 | Re-Issued for Review | KVZ | TB | RAR | |||||
| 4 | 05-30-2018 | Issued for Purchase | KVZ | TB | RAR | |||||
| 5 | 06-11-2018 | Re-Issued for Purchase | KVZ | TB | RAR | |||||
| PART 2 - PRODUCTS | |||
| Inverter – TMEIC Samurai | |||
| Model #: TMEIC – Samurai Series (PVL-L1833GRM) | |||
| INPUT (DC) @ 40 deg C Ambient | |||
| Max input current | 3091 A | ||
| Max input voltage | 1000 V (Open Circuit) | ||
| MPPT range | 605 - 950 V | ||
| Number of MPP trackers | 1 | ||
| Array Topology | Solidly Grounded Negative | ||
| DC Entry | Bottom - through removable floor plate. Floor plate shall be pre-punch and supplied with (16) 3in. male terminal adapters and sealing lock nuts (refer to Attachment ‘C’). | ||
| DC Overcurrent Protective Devices | PV Listed Fuse Qty of ( | ) per Inverter – | |
| Refer to Table #1 for exact fuse quantities | |||
| DC Termination Provisions | Provide for the direct termination of (2) 1/C - #4/0 Al PV wire per pole for each input (i.e. four conductors per input) | ||
| Ground Fault Circuit Interrupter | Yes | ||
| OUTPUT @ 40 deg C Ambient | |||
| Mains voltage | 3 x 418 Vac (+ 10% /- 12%) | ||
| Mains frequency | 60 Hz | ||
| Rated power | 1,833 kW / 2,000 kVA | ||
| Rated Output Current | 2,762 at 40 C | ||
| Power factor range | Adjustable (0 to 1 lead/lag) | ||
| Current harmonic distortion | < 5% at rated power | ||
| Auxiliary power supply | Self-Consumption: As Required by TMEIC For Customer use: 120/208 Vac, 3 PH, 4W, 5kVA NEMA 3R XFMRs, safety switches and distribution equipment | ||
| Reactive Power Range (40C, 1PU Grid Voltage) | +/- 800 kVAR up to 1833kW | ||
| EFFICIENCY | |||
| Max efficiency (without aux) | 98.8% | ||
| Weighted CEC efficiency | 98.5% | ||
| Standby power consumption (max) | < 295 W | ||
| MECHANICAL DATA | |||
| Enclosure | NEMA 3R | ||
| Dimensions (HxWxD) | 2283 x 5000 x 1150 mm | ||
| Weight | 6,000 kg (13,228 lbs) | ||
| Cooling | Hybrid liquid / air-cooled | ||
| DC Disconnects Per 690.16 | Yes | ||
| AMBIENT SPECIFICATIONS | |||
| Model #: TMEIC – Samurai Series (PVL-L1833GRM) | |||
| Ambient operating temperature | -20°C to +55°C | ||
| Rel. humidity | No condensation from 5% to 95% | ||
| Max altitude | 2000 m without derating | ||
| PROTECTION & MONITORING | |||
| Zone Monitoring | Yes – provide current monitoring of all ( | : | |
| Customer Data Access | Provide access to all MODBUS registers | ||
| Grid monitoring | Adjustable voltage and frequency range | ||
| PV generator connection | Per IEEE-1547 & UL-1741 | ||
| INTERFACES | |||
| Communications interface | True ModBus® over TCP/IP – Converter from RS232 Not Allowed | ||
| Communications Hub | Included in one inverter per PCS consisting of an Ethernet switch, I/O for XFMR alarms Transformer and inverter data points available over MODBUS TCP/IP | ||
| I/O Cable Assemblies | Preconnectorized cable assemblies to connect XFMR I/O to communications hub and power and signal cable to aux power panel | ||
| STANDARDS & CERTIFICATIONS | |||
| Safety | IEEE-1547, UL 1741 | ||
| Electromagnetic compatibility | IEEE 1547. FCC Part 15A | ||
| Grid management | As required per local utility per project | ||
| Output Metering | Three-phase AC voltage and current, power factor, frequency, instantaneous power, kWh production, and any available faults and alarms. | ||
| Medium-Voltage Step-up Transformer | |||
| Type | Liquid-Filled Padmounted Transformer (Outdoor Rated NEMA 3R) - Two Winding | ||
| Standards | IEEE/ANSI C57.12.00, UL Listed as step up XFMR | ||
| Standards | NEC 2014 for auxiliary equipment, conductor and conduit installations. | ||
| Fluid | Natural Biodegradable Fluid (FR3 or equivalent) | ||
| Cooling Class | KNAN | ||
| Core | Grain Oriented Steel | ||
| Number of Windings | 2 Winding; H, X | ||
| Phase | 3 Phase | ||
| Frequency | 60 Hz | ||
| Average Winding Rise | 55/65 °C | ||
| Avg. Ambient Temperature | 40 °C | ||
| Medium-Voltage Step-up Transformer | |
| Max Ambient Temperature | 50°C |
| %Z | 5.75% nominal (+/- 7.5% Per ANSI) |
| NL Loss @ 20 °C | TBD W |
| Load Loss @ 85 °C | TBD W @ 95 °C |
| CEC Weighted Efficiency | 99.1% @ 100% Load @ 85 °C |
| Power Rating(s) | 2,000 kVA |
| High Voltage | 34.5 kV Delta |
| High Voltage Taps | 0.95, 0.975, 1.0, 1.025, & 1.05 per unit |
| High Voltage BIL | 150kV BIL minimum (Per ANSI/IEEE based on Primary Voltage) |
| Surge Arrestor | Not provided with a transformer |
| Low Voltage | 418 Vac Y |
| Low Voltage BIL | 30kV BIL |
| Over Voltage | 105% OV at Full Load per ANSI/IEEE Standard |
| Feed Configuration | Dead Front – 600A Deadbreak, Loop Configuration (6 bushings) w/6 parking stands |
| Color | Match Inverter |
| Tank and Cabinet | Dry Nitrogen Blanket Zone D (4) Seismic Rating Penta-head Cabinet Handle Bolt Tank cover/handhole may be bolted or welded |
| HV Bushings | Oil to air epoxy |
| LV Bushings | Close Coupled with inverter - custom throated connection to mate directly with the inverter. |
| Fuses | Factory-installed match melt fusing consisting of under oil current-limiting fuse in series with BAY-O-NET type weak link expulsion fuse - sized by manufacturer per rating |
| Switches | 2-Position, fully-rated, LBOR Transformer Switch (Primary) with Lock-Out Tag-Out Provisions located in the external pad-lockable box. Operable without exposure to live parts. LBOR switch operator must be outside of HV compartment. |
| Monitoring | Pressure Relief Valve Liquid Level Gauge with Alarm Contacts Pressure / Vacuum Gauge with Alarm Contacts Thermometer with Alarm Contacts Gauges and alarm contact terminations to be located in an accessible location not exposed to live parts |
| Revenue Grade Meter | Not Included |
| Fittings | Drain Sampling Valve located in an accessible location not exposed to live parts and inside a lockable enclosure. Main drain valve - may be located within the LV Compartment, where convenient |
| Markings | UL Certified Label External Nameplate - Stainless Steel "Non-PCB" Label "For Use in Step-Up and Step-Down Applications" Label "Danger-High Voltage - Keep Out " Warning Label |
| Production Tests | Refer to section 1.6.3 |
| Warranty | 5-year Standard Warranty |
| Elevation | < 1000 m |
| Other | Standard E-coat & powder paint process Schrader valve Oil sample valve External ground pad |
| PCS Skid – Auxiliary Rack Components | ||
| Auxiliary Power | ||
| DESCRIPTION | RATING | |
| Voltage | 120/208, 3 PH, 4 W derived from inverter 418 Vac 3-Phase bus | |
| Components | ||
| Aux Transformer | 30 kVA XFMR with 5kVA dedicated to 120/208V. The remaining 25 kVA is for 480V., NEMA 3R (not installed) | |
| Panelboard | NEMA 3R – 120/208, 3 PH, 4W, 20AMCB, (18) Ckt w/ (5) 1P 15A and (1) 1P – 20A bolt on CBs | |
| Safety Switch | NEMA 3R | |
| Lighting | None | |
| Receptacles | (2) Double Duplex, GFCI, 20A, in WP enclosure fed from (1) 1P-20A Brk. Nipple WP box to panelboard | |
| Free Standing Aux Equipment Support | Galvanized steel – Used to mount the safety switch and panelboard. Leave the remaining area of the rack for Owner furnished and field mounted equipment, including Network Control Units (NCUs) and antennas. | |
| Quantity | : | 12 Units |
| Product Location | : | |
| Condition | : | N/A |
| Condition Description | : | Being sold "AS IS, WHERE IS". Buyer is responsible for shipping and handling. |
| Manufacturer | : | |
| | : | |
| Trader | Ana Santos +1 832 384 9940 | |
| Seller | : | |
| Seller Industry | : | |
Salvex is a prominent global e-commerce platform specializing in the sale of surplus commercial assets. We collaborate with thousands of companies, both publicly traded and private, spanning 200 countries worldwide. Our expertise lies in repurposing renewable energy equipment and solar panels sourced from insurance claims, corporate surpluses, asset recoveries, bankruptcies, and natural disasters. We identify markets across North America, South America, Europe, Africa, the Middle East, Asia, and Oceania. Through our global sustainability initiatives, we contribute to environmental preservation by implementing carbon offset strategies through asset repurposing. We look forward to assisting your company in finding exceptional deals by showcasing surplus assets that align with your requirements.