These Solar Power Conversion Stations for Grid-Connected Application units are no longer needed for the company's own operation and is being sold as an asset liquidation for its owner.
Rev | Date | Description | BY | CHK | APP | |||||
A | 05-08-2018 | Issued for Review | KVZ | TB | RAR | |||||
B | 05-10-2018 | Issued for Review | KVZ | TB | RAR | |||||
0 | 05-11-2018 | Issued for Purchase | KVZ | TB | RAR | |||||
1 | 05-11-2018 | Re-Issued for Purchase | KVZ | TB | RAR | |||||
2 | 05-22-2018 | Issued for Review | KVZ | TB | RAR | |||||
3 | 05-24-2018 | Re-Issued for Review | KVZ | TB | RAR | |||||
4 | 05-30-2018 | Issued for Purchase | KVZ | TB | RAR | |||||
5 | 06-11-2018 | Re-Issued for Purchase | KVZ | TB | RAR |
PART 2 - PRODUCTS | |||
Inverter – TMEIC Samurai | |||
Model #: TMEIC – Samurai Series (PVL-L1833GRM) | |||
INPUT (DC) @ 40 deg C Ambient | |||
Max input current | 3091 A | ||
Max input voltage | 1000 V (Open Circuit) | ||
MPPT range | 605 - 950 V | ||
Number of MPP trackers | 1 | ||
Array Topology | Solidly Grounded Negative | ||
DC Entry | Bottom - through removable floor plate. Floor plate shall be pre-punch and supplied with (16) 3in. male terminal adapters and sealing lock nuts (refer to Attachment ‘C’). |
||
DC Overcurrent Protective Devices | PV Listed Fuse Qty of ( | ) per Inverter – | |
Refer to Table #1 for exact fuse quantities | |||
DC Termination Provisions | Provide for the direct termination of (2) 1/C - #4/0 Al PV wire per pole for each input (i.e. four conductors per input) |
||
Ground Fault Circuit Interrupter | Yes | ||
OUTPUT @ 40 deg C Ambient | |||
Mains voltage | 3 x 418 Vac (+ 10% /- 12%) | ||
Mains frequency | 60 Hz | ||
Rated power | 1,833 kW / 2,000 kVA | ||
Rated Output Current | 2,762 at 40 C | ||
Power factor range | Adjustable (0 to 1 lead/lag) | ||
Current harmonic distortion | < 5% at rated power | ||
Auxiliary power supply | Self-Consumption: As Required by TMEIC For Customer use: 120/208 Vac, 3 PH, 4W, 5kVA NEMA 3R XFMRs, safety switches and distribution equipment |
||
Reactive Power Range (40C, 1PU Grid Voltage) |
+/- 800 kVAR up to 1833kW | ||
EFFICIENCY | |||
Max efficiency (without aux) | 98.8% | ||
Weighted CEC efficiency | 98.5% | ||
Standby power consumption (max) | < 295 W | ||
MECHANICAL DATA | |||
Enclosure | NEMA 3R | ||
Dimensions (HxWxD) | 2283 x 5000 x 1150 mm | ||
Weight | 6,000 kg (13,228 lbs) | ||
Cooling | Hybrid liquid / air-cooled | ||
DC Disconnects Per 690.16 | Yes | ||
AMBIENT SPECIFICATIONS | |||
Model #: TMEIC – Samurai Series (PVL-L1833GRM) | |||
Ambient operating temperature | -20°C to +55°C | ||
Rel. humidity | No condensation from 5% to 95% | ||
Max altitude | 2000 m without derating | ||
PROTECTION & MONITORING | |||
Zone Monitoring | Yes – provide current monitoring of all ( | : | |
Customer Data Access | Provide access to all MODBUS registers | ||
Grid monitoring | Adjustable voltage and frequency range | ||
PV generator connection | Per IEEE-1547 & UL-1741 | ||
INTERFACES | |||
Communications interface | True ModBus® over TCP/IP – Converter from RS232 Not Allowed | ||
Communications Hub | Included in one inverter per PCS consisting of an Ethernet switch, I/O for XFMR alarms Transformer and inverter data points available over MODBUS TCP/IP |
||
I/O Cable Assemblies | Preconnectorized cable assemblies to connect XFMR I/O to communications hub and power and signal cable to aux power panel |
||
STANDARDS & CERTIFICATIONS | |||
Safety | IEEE-1547, UL 1741 | ||
Electromagnetic compatibility | IEEE 1547. FCC Part 15A | ||
Grid management | As required per local utility per project | ||
Output Metering | Three-phase AC voltage and current, power factor, frequency, instantaneous power, kWh production, and any available faults and alarms. |
||
Medium-Voltage Step-up Transformer | |||
Type | Liquid-Filled Padmounted Transformer (Outdoor Rated NEMA 3R) - Two Winding |
||
Standards | IEEE/ANSI C57.12.00, UL Listed as step up XFMR | ||
Standards | NEC 2014 for auxiliary equipment, conductor and conduit installations. | ||
Fluid | Natural Biodegradable Fluid (FR3 or equivalent) | ||
Cooling Class | KNAN | ||
Core | Grain Oriented Steel | ||
Number of Windings | 2 Winding; H, X | ||
Phase | 3 Phase | ||
Frequency | 60 Hz | ||
Average Winding Rise | 55/65 °C | ||
Avg. Ambient Temperature | 40 °C |
Medium-Voltage Step-up Transformer | |
Max Ambient Temperature | 50°C |
%Z | 5.75% nominal (+/- 7.5% Per ANSI) |
NL Loss @ 20 °C | TBD W |
Load Loss @ 85 °C | TBD W @ 95 °C |
CEC Weighted Efficiency | 99.1% @ 100% Load @ 85 °C |
Power Rating(s) | 2,000 kVA |
High Voltage | 34.5 kV Delta |
High Voltage Taps | 0.95, 0.975, 1.0, 1.025, & 1.05 per unit |
High Voltage BIL | 150kV BIL minimum (Per ANSI/IEEE based on Primary Voltage) |
Surge Arrestor | Not provided with a transformer |
Low Voltage | 418 Vac Y |
Low Voltage BIL | 30kV BIL |
Over Voltage | 105% OV at Full Load per ANSI/IEEE Standard |
Feed Configuration | Dead Front – 600A Deadbreak, Loop Configuration (6 bushings) w/6 parking stands |
Color | Match Inverter |
Tank and Cabinet | Dry Nitrogen Blanket Zone D (4) Seismic Rating Penta-head Cabinet Handle Bolt Tank cover/handhole may be bolted or welded |
HV Bushings | Oil to air epoxy |
LV Bushings | Close Coupled with inverter - custom throated connection to mate directly with the inverter. |
Fuses | Factory-installed match melt fusing consisting of under oil current-limiting fuse in series with BAY-O-NET type weak link expulsion fuse - sized by manufacturer per rating |
Switches | 2-Position, fully-rated, LBOR Transformer Switch (Primary) with Lock-Out Tag-Out Provisions located in the external pad-lockable box. Operable without exposure to live parts. LBOR switch operator must be outside of HV compartment. |
Monitoring | Pressure Relief Valve Liquid Level Gauge with Alarm Contacts Pressure / Vacuum Gauge with Alarm Contacts Thermometer with Alarm Contacts Gauges and alarm contact terminations to be located in an accessible location not exposed to live parts |
Revenue Grade Meter | Not Included |
Fittings | Drain Sampling Valve located in an accessible location not exposed to live parts and inside a lockable enclosure. Main drain valve - may be located within the LV Compartment, where convenient |
Markings | UL Certified Label External Nameplate - Stainless Steel "Non-PCB" Label "For Use in Step-Up and Step-Down Applications" Label "Danger-High Voltage - Keep Out " Warning Label |
Production Tests | Refer to section 1.6.3 |
Warranty | 5-year Standard Warranty |
Elevation | < 1000 m |
Other | Standard E-coat & powder paint process Schrader valve Oil sample valve External ground pad |
PCS Skid – Auxiliary Rack Components | ||
Auxiliary Power | ||
DESCRIPTION | RATING | |
Voltage | 120/208, 3 PH, 4 W derived from inverter 418 Vac 3-Phase bus | |
Components | ||
Aux Transformer | 30 kVA XFMR with 5kVA dedicated to 120/208V. The remaining 25 kVA is for 480V., NEMA 3R (not installed) |
|
Panelboard | NEMA 3R – 120/208, 3 PH, 4W, 20AMCB, (18) Ckt w/ (5) 1P 15A and (1) 1P – 20A bolt on CBs |
|
Safety Switch | NEMA 3R | |
Lighting | None | |
Receptacles | (2) Double Duplex, GFCI, 20A, in WP enclosure fed from (1) 1P-20A Brk. Nipple WP box to panelboard |
|
Free Standing Aux Equipment Support |
Galvanized steel – Used to mount the safety switch and panelboard. Leave the remaining area of the rack for Owner furnished and field mounted equipment, including Network Control Units (NCUs) and antennas. |